Question: Should the insulation be turned around?
Answer: Yes, the facing should face the interior or warm side of the room. The only exception is in high humidity areas such as Florida.
Answer: Yes, the facing should face the interior or warm side of the room. The only exception is in high humidity areas such as Florida.
What kind of a vapor barrier should I put on the gable end? Since it is brick, do I put it against the brick before putting up the studs, or after the studs and insulation?
For the ceiling, what kind of vapor barrier do I put on?"
Answer: Use a Kraft-faced insulation facing the warm air. The Kraft facing will be in direct contact with your drywall.
Would a layer of 2x6 insulation and a layer of 2x4 insulation give me more r value? I know that I could attach a 2x4 furring strip and put the R-30 2x10 insulation in, but I don't want to do that if possible."
Answer: Yes. Two layers of R-15 uncompressed will give you R-30. Adding R-19 and R-13 insulation without furring out the rafters would compress to approximately R-25.
Furring out with 2x4's would be the proper way to do this. This would allow the proper space for sufficient R-Value.
Answer: Owens Corning no longer manufactures a polyisocyanurate insulation so I can't help with that question. You could use FOAMULAR® insulation but you will have to get an OK from your local building inspector to leave it exposed.
Answer: Use the same method as a crawl space under floor application. For extra protection against critters, I suggest insulation netting.
Answer: The facing should face the warm air. This is very simple to fix; just flip the insulation so the facing is up towards the upstairs.
Answer: I don't think I understand the problem. If the attic is insulated properly with the raft-R-mate® atticrafter vents installed and blocked correctly, you should not be able to see the soffit from the inside of the attic.
Answer: If you use foam and tape the seams, it qualifies as a weather resistant barrier. Therefore, you will not need housewrap. You will have to go to the manufacturer of your windows to find out about the jamb size availability.
Answer: All extruded polystyrene foam insulation products must be covered with a 15-minute thermal barrier. You will need to check with manufacturer of the paneling to see if that product qualifies.
You may find it to be less labor intensive if you use fiberglass batt insulation for your project. The InsulPINK insulation was not designed for the application which you are doing. InsulPINK insulation is designed to be used on masonry surfaces. It has channels that allow for furring strips to be used as nailers.
Answer: The only thing I can think of to suggest is building out the current construction to provide more space for insulation. For example, if you build out the current framing with 2x6's you would have enough space to accommodate an R-30 insulation.
In order to get the metal siding to stand proud of the masonry veneer wall below we need to install 3" 'Z' girts over the Codebord® add generic. My question is: Is there enough compressive strength in the Codebord® add generic to allow for sufficient resistance against wind loading when the girt is fastened to the steel stud through the Codebord® add generic?"
Answer: I can't evaluate the overall strength of the system you are proposing but I can tell you the compressive strength of Owens Corning Codebord® add generic available in Canada is 20.
Answer: You can use Owens Corning Bild-R-Tape® construction tape or any other good construction tape. Do not use duct tape because it will not retard vapor movement.
Answer: We have not tested both products together so I cannot offer accurate data. If FOAMULAR® Insulation is applied and the seams are taped, this would act as a weather resistant barrier and there would be no need for housewrap.
Answer: Blowing insulation into the enclosed cavities of walls and ceilings is generally not a good do-it-yourself project because the walls or ceiling could be damaged by an inexperienced operator. We recommend hiring a contractor for this project.
My question is - Is a plastic vapor barrier still needed prior to the drywall? Or does the high density insulation act as a barrier? I am concerned about making a moisture trap."
Answer: High density fiberglass insulation is not a vapor retarder. I am not sure what type of "high density foam" you have installed? Is it an Owens Corning product such as FOAMULAR® Extruded Polystyrene Insulation? If not, you may want to check with the manufacturer of that product.
Answer: Yes, you can use FOAMULAR® Insulation in this application. Make sure to penetrate to the wood studs when attaching the FOAMULAR Insulation. Also, make sure to penetrate the wood studs when attaching the siding.
Answer: It sounds like the add-on rooms were never insulated. I would have an insulation professional come inspect and make recommendations. You can find an Owens Corning Certified Energy Professional® contractor by checking the Web site.
Answer: If you are going to lay down 2x4's, I suggest Kraft-faced insulation with the vapor retarder up towards the living area stapled to the face. I would not use a moisture barrier on the concrete floor. This could cause trapped moisture between the Kraft paper and concrete.
Answer: There is a Compression Chart on the Owens Corning Web site that indicates the R-values that result when insulation is compressed in a cavity. In your case, the R-13 insulation you plan to install will be reduced to R-10.
Answer: If you are able to install the soffit vents from the outside I see no problem in doing so. You should be able to staple half of the vent from the outside and maybe half from the inside. Glue is not a recommendation.
Installing the soffit vent is important because that is where air will enter the attic. The ridge vents act as the attic's exhaust.